4.5 ASG100 test signal generator
ASG100 test signal generator uses a 32-bit microprocessor chip and a high-precision signal generation circuit,It can generate a specific test signal.When the monitored IT system insulation fault occurs , It start and generate a test signal timely ,and it work with insulation fault locator to achieve insulation fault location.
Technical Parameters
Auxiliary power | Voltage | DC24V(±25%) |
The maximum power consumption | ≤2VA | |
system be monitored | Rated voltage | AC 220 V(±10%) |
Rated frequency | 45 ~ 60Hz | |
Positioning signals | Current Location | <1mA r.m.s. |
Communications | Bus | CAN |
Protocol | Custom protocol
|
Overall and installation dimensions(unit:mm)
4.6 AIL100 Series insulation fault locator
AIL100-4/AIL100-8 insulation fault locator uses high-precision signal detection circuit with high sensitivity transformer,It detects ASG100 test signal generator’s signal which is injected into the system,It can accurately locate the insulation fault circuit. Among them, AIL100-4 insulation fault locator can locate insulation faults of four loops,AIL100-8 insulation fault locator can locate insulation faults of eight loops.
Parameters | Values | ||
AIL100-4 | AIL100-8 | ||
Auxiliary power | Voltage | DC24V(±25%) | |
The maximum power consumption | ≤2VA | ||
Monitored system | Rated voltage | AC 220 V(±10%) | |
Frequency | 45 ~ 60Hz | ||
Positioning signals | Location voltage | <25V a.c.r.m.s. | |
Location current | <1mA r.m.s. | ||
Fault location | The maximum number of loops | 4 | 8 |
Response time | <2s | ||
Communications | Bus | CAN | |
Protocol | Custom protocol |
Overall and installation dimensions(unit:mm)